Installers Contact Us Help Spares Outlet Store

HBN 00-10 HTM64 (TB H6) Markwik 21 Demountable Panel Mixer, Time Flow Sensor

A6245(AA) Markwik 21 integral thermostat, demountable panel mixer, time flow sensor, detachable spout and Armitage Bioguard outlet fitted

(TB H6). Demountable panel mixer tap, removable spout fitted with Armitage Shanks Bioguard outlet. Integral thermostat, time flow sensor operation and single flow horizontal nozzle particularly suited for use with Scrub up troughs. Insulated technology keeps the ‘hot’ side of the mixer at a safe surface temperature. Includes thermal disinfection features, available with removable spout for autoclave sterilisation, body demounts from legs or panel for submergible disinfection and  Bioguard outlet also helps protect against bacteria. Optional adapter for interchangeable filter.


  • Medical and healthcare use
  • Timed flow sensor operation
  • Built in isolation valves
  • Front access D-08 auditing & servicing
  • Thermal disinfection features
  • Demount, submerge and disinfect
  • Bioguard against bacteria
  • Auto-Flush technology
  • Available with fixed or detachable spout

  • Chrome
    (AA)
Material: Chrome Plated Metal
Weight: 5.80Kg
Flow rate: 7.5 Litres per minute @ 3 bar pressure
HTM code: TB H6

Standards: Conforms to HBN 00.10, HBN 00.09 and HTM 04-01 Addendum 2013.

  • 1512003

View data sheet  

Brassware

A6245(AA) (TB H6) Markwik 21 integral thermostat, demountable panel mixer, time flow sensor, detachable spout and Armitage Bioguard outlet fitted

Variants

Special notes

This product is fitted with an Armitage Bioguard outlet which reduces the opportunity for bio film attachment and is lined with anti-microbial copper. Tap is activated by hand movement over the sensor and water will run for a predetermined length of time, factory pre-set at 1 minute but adjustable. Hygienic automatic flush can be set to occur every 6, 12, 24, 48 or 72 hours. Unique built-in thermal disinfection cleansing feature using kit S8239NU a bridging hose which is re-usable. A purging tool A4556AA is also available to facilitate initial installation or aid in system disinfection. Flow rate regulated to maximum of 10 Litres per minute. * Line drawing shows recommended height over scrub up troughs.